KVA Calculator - Apparent, Real, and Reactive Power
Use this kVA calculator to convert RMS voltage, current, and power factor into apparent kVA, real kW, and reactive kVAr for single or three-phase AC loads.
kVA Calculator
Results
What Is the kVA Calculator?
A kVA calculator turns RMS voltage and current into apparent power in kilovolt-amperes, then splits that apparent power into real kilowatts and reactive kVAr through the power factor. It accepts single-phase and three-phase inputs because the same answer needs different multipliers, and reports the result in kVA, kW, and kVAr on one screen.
- • Sizing a UPS or generator for a known load: Convert a nameplate current and voltage into the kVA figure that a UPS spec sheet quotes, then read off the kW the load will actually draw.
- • Working with three-phase industrial mains: Convert 400 V line-to-line or 230 V line-to-neutral industrial measurements into apparent kVA and real kW for motors and panel feeds.
- • Estimating power-factor penalties: Compare kW at the measured PF with kVA to see how much apparent power the chosen PF leaves on the table.
- • Translating clamp-meter readings: Turn a clamp-meter current reading at a known supply voltage into kVA, kW, and kVAr without re-deriving the current type.
AC power differs from DC because the voltage and current oscillate and may not peak together. The wiring still has to carry the full apparent power in kVA even when only the real power in kW does useful work. The kVA calculator makes that split visible by computing kVA first and then kW and kVAr from the power factor.
When you need the same answer in watts, volt-amperes, and var, AC Wattage Calculator reports the wattage, VA, and var for the same single-phase and three-phase inputs.
How the kVA Calculator Works
The calculator picks a phase factor k from the current-type selector, multiplies k by the RMS voltage and current to get apparent power S in volt-amperes, then divides S by 1000 to convert it to kVA. It also multiplies S by the power factor to get real power P in kW and computes reactive power Q in kVAr from the sqrt(1 - PF^2) share of S.
- V: RMS voltage in volts. Use V_LL for three-phase line-to-line or V_LN for three-phase line-to-neutral.
- I: RMS current the AC load draws, in amperes, from a clamp meter or nameplate.
- PF: Power factor, the cosine of the phase angle between voltage and current. 1.0 for a pure resistor, 0.8 to 0.95 for typical induction motors.
- k: Phase factor from the current-type selector: 1 for single-phase, sqrt(3) for three-phase line-to-line, 3 for three-phase line-to-neutral.
- S: Apparent power in kVA, equal to k * V * I / 1000. Sets wiring, transformer, generator, and UPS sizing.
- P: Real power in kW, equal to S * PF. The number used for energy billing and useful work.
- Q: Reactive power in kVAr, equal to S * sqrt(1 - PF^2). Oscillates between source and load and is reduced by PF correction.
The three apparent-power formulas share the shape S_kVA = k * V * I / 1000, with k = 1, sqrt(3), or 3. S is what the wiring carries, P is what gets billed, and Q is what PF correction reduces.
120 V single-phase circuit at 10 A and 0.85 PF
Current type: single-phase. Voltage: 120 V. Current: 10 A. Power factor: 0.85.
k = 1. S = 1 * 120 * 10 / 1000 = 1.2 kVA. P = 1.2 * 0.85 = 1.02 kW. Q about 0.632 kVAr.
1.2 kVA, 1.02 kW, 0.632 kVAr.
Typical 120 V workshop circuit. The wiring still carries the full 1.2 kVA even though only 1.02 kW of useful work is delivered.
400 V three-phase line-to-line motor at 50 A and 0.9 PF
Current type: three-phase line-to-line. Voltage: 400 V. Current: 50 A. Power factor: 0.9.
k = sqrt(3) about 1.732. S about 34.64 kVA. P about 31.18 kW. Q about 15.10 kVAr.
34.64 kVA, 31.18 kW, 15.10 kVAr.
European 400 V three-phase motor. A PF-correcting capacitor bank can lift the power factor closer to 1.0 and shrink Q.
According to Wikipedia - AC Power, the apparent power in an AC circuit equals the product of RMS voltage and RMS current, and the real power is the apparent power multiplied by the cosine of the phase angle.
According to Wikipedia - Three-Phase Electric Power, balanced three-phase apparent power is S = sqrt(3) * V_LL * I and the corresponding real power is P = sqrt(3) * V_LL * I * cos(phi).
When the power factor itself is the unknown and you have to back it out from real kW and apparent kVA, Power Factor Calculator returns PF, the phase angle, and the reactive kVAr from the same two inputs you see here.
Key Concepts Explained
Four ideas cover most apparent-power problems in physics, motor sizing, and UPS selection.
Apparent, real, and reactive power
Apparent power S in kVA is the product of RMS voltage, RMS current, and the phase factor divided by 1000. Real power P in kW is S times the power factor. Reactive power Q in kVAr is S times sqrt(1 - PF^2).
Power factor
Power factor is the cosine of the phase angle between voltage and current. A value of 1.0 means every kVA becomes a kW. A value of 0.85 means 15% is reactive, so 1000 kVA delivers 850 kW.
RMS voltage and current
AC meters report RMS values that represent the equivalent heating effect of the alternating waveform. Using RMS values in the apparent-power formula matches the integral of v(t) * i(t) over a cycle.
Three-phase and the sqrt(3) factor
In a balanced three-phase system the line-to-line voltage is sqrt(3) times the line-to-neutral voltage. The same sqrt(3) factor appears in three-phase line-to-line kVA because S = 3 * V_LN * I and V_LL = sqrt(3) * V_LN.
These four ideas carry over to any apparent-power problem, from UPS selection to power-quality work.
When the next step is to convert the kW into mechanical work over a measured time interval, Work Energy Power Calculator carries the same kilowatts through the work-energy-power formulas.
How to Use the kVA Calculator
Five steps from a measured voltage, current, and power factor to a complete apparent-power answer in kVA, kW, and kVAr.
- 1 Pick the current type: Choose single-phase for typical 120 V or 240 V household circuits, three-phase line-to-line for industrial 400 V mains, or three-phase line-to-neutral for phase voltage only.
- 2 Enter the RMS voltage: Type the RMS voltage from the meter or nameplate. Use V_LL for three-phase line-to-line or V_LN for three-phase line-to-neutral.
- 3 Enter the RMS current: Type the RMS current the load draws, in amperes, from a clamp-meter reading on the supply side.
- 4 Enter the power factor: Pick a power factor between 0 and 1. Use 1.0 for resistive loads, 0.85 to 0.95 for typical induction motors at full load.
- 5 Read the results: The result panel shows kVA, kW, kVAr, the power factor used, the percentage of apparent power lost to the power factor, the phase angle in degrees, and the phase factor k.
Practical example: a 240 V single-phase workshop circuit draws 20 A at 0.8 PF. Type 240 V, 20 A, and PF 0.80, and the calculator returns 4.8 kVA, 3.84 kW, 2.88 kVAr, and 20% power-factor loss.
When sizing branch circuits from the apparent-power result, Electrical Load Calculator returns the running and starting load in amps from the same voltage and power factor.
Benefits of Using This Calculator
An apparent-power workflow catches the cases where multiplying volts by amps would quote a real-power number the wiring cannot deliver.
- • Three current-type modes in one tool: Switch between single-phase, three-phase line-to-line, and three-phase line-to-neutral without retyping values.
- • Apparent, real, and reactive power in one screen: kVA, kW, and kVAr are computed side by side, so the power factor role in UPS and generator sizing is visible without switching pages.
- • Output units match industry spec sheets: Generator and UPS manufacturers quote capacity in kVA, so the result lines up directly with the rating plate instead of forcing a unit conversion.
- • Input validation with status notes: Out-of-range power factors, zero inputs, and unusual voltage combinations surface clear status notes.
- • Cross-validation-friendly defaults: The default 120 V / 10 A / 0.85 PF example returns 1.2 kVA, matching the textbook single-phase example.
The same kVA, kW, and kVAr split is what you see on UPS nameplates as 'VA rating' versus 'W rating' and in utility tariffs as 'PF penalty threshold'.
When you also need the resistance of the wiring or the resistive part of the load, Ohm's Law Calculator returns V, I, R, and P for any two of the four so you can sanity-check the voltage drop across the run.
Factors That Affect Your Results
Five factors shape the apparent kVA on the result panel, plus two limitations worth knowing.
Power factor
Raising the power factor from 0.7 to 1.0 increases the real kW by 43% for the same kVA and voltage.
RMS voltage and current accuracy
Apparent kVA scales linearly with V and I. A 5% error in RMS voltage becomes a 5% error in kVA.
Current-type selector
Switching between single-phase and three-phase line-to-line changes the multiplier from 1 to sqrt(3).
Harmonics and non-linear loads
Rectifier loads and VFDs draw non-sinusoidal current, so the displacement power factor captured by cos(phi) can run higher than the IEEE 1459 total power factor.
Unbalanced three-phase loads
The three-phase formulas assume balanced phase currents. If one phase draws much more than the others, the result is a balanced-load approximation.
- • The formula assumes sinusoidal voltage and current at a single fundamental frequency. Distorted waveforms from large rectifier banks need a power-quality meter.
- • Real three-phase installations are rarely perfectly balanced, so the k * V * I / 1000 shortcut is a planning estimate.
In teaching, the single-frequency, balanced-load assumption matches textbook examples. In the field, treat the answer as a planning number and confirm with a power analyzer before specifying a UPS or generator.
According to OpenStax University Physics Volume 2, Section 15.4 - Power in an AC Circuit, average AC power equals rms current times rms voltage times cos(phi), so a 5% error in the RMS reading flows through to a 5% error in the real kW.
When the apparent kVA feeds a standby generator and you need a sizing recommendation in kVA or kW, Generator Size Calculator turns the same inputs into a recommended generator rating.
Frequently Asked Questions
Q: How do I calculate kVA from volts and amps?
A: Multiply the RMS voltage by the RMS current to get the apparent power in volt-amperes, then divide by 1000 to convert to kVA. For three-phase line-to-line use kVA = sqrt(3) * V_LL * I / 1000. For three-phase line-to-neutral use kVA = 3 * V_LN * I / 1000. The kVA figure is what a generator or UPS nameplate quotes, while the real kW is kVA times the power factor.
Q: What is the difference between kVA and kW?
A: kVA is the apparent power that the supply has to deliver, equal to RMS voltage times RMS current times the phase factor divided by 1000. kW is the real power that does useful work, equal to kVA times the power factor. A motor with PF = 0.85 drawing 10 kVA will deliver 8.5 kW of useful mechanical work, and the supply still has to carry the full 10 kVA.
Q: How do I convert kVA to kW with a power factor?
A: Multiply kVA by the power factor to get kW. For example 50 kVA at PF = 0.9 returns 45 kW. The remaining 50 * sqrt(1 - 0.9^2) = 21.8 kVAr is reactive power that oscillates between the source and the load and does no useful work.
Q: What is the three-phase kVA formula?
A: For a balanced three-phase line-to-line connection the formula is S_kVA = sqrt(3) * V_LL * I / 1000. For a line-to-neutral connection it is S_kVA = 3 * V_LN * I / 1000. The two are equivalent because V_LL = sqrt(3) * V_LN in a balanced system, so the sqrt(3) and 3 factors appear depending on which voltage you measured.
Q: How do I find kVAr from kVA?
A: Multiply kVA by sqrt(1 - PF^2) to get reactive kVAr. For example 100 kVA at PF = 0.8 returns 100 * sqrt(1 - 0.64) = 60 kVAr. Capacitor banks sized to deliver 60 kVAr of leading reactive power will lift the power factor closer to 1.0 and shrink the apparent kVA the supply has to deliver.
Q: Why do generators and UPS systems use kVA instead of kW?
A: Generators and UPS systems are sized by the heating effect of the current they carry, which is set by apparent power in kVA, not by the real kW the load draws. A generator rated 100 kVA can deliver up to 100 kW only at power factor 1.0; at PF = 0.8 the same unit still carries 100 kVA but only delivers 80 kW of useful power.