Vapor Pressure Deficit Calculator - Temperature and Humidity to VPD

Use this vapor pressure deficit calculator to find saturation, actual, and deficit vapor pressure from air temperature and relative humidity.

Updated: June 18, 2026 • Free Tool

Vapor Pressure Deficit Calculator

Air temperature in degrees Celsius. Use negative values for cold-storage or winter-air estimates.

%

Relative humidity of the surrounding air, between 0 and 100 percent. Values outside the range are clamped to the nearest valid bound.

Results

Vapor Pressure Deficit (VPD)
0kPa
Saturation Vapor Pressure (SVP) 0kPa
Actual Vapor Pressure (AVP) 0kPa
Vapor Pressure Deficit (mbar) 0mbar
Plant-Stage Band 0

What Is the Vapor Pressure Deficit Calculator?

The vapor pressure deficit calculator turns a single air temperature and relative humidity reading into three pressures: the saturation vapor pressure the air could hold, the actual vapor pressure it does hold, and the deficit between them. It uses the FAO-56 Magnus-Tetens equation so the result matches the tables printed in irrigation, greenhouse, and HVAC references, and it labels the result with a plant-stage band. Use it to plan greenhouse setpoints, set indoor humidity targets, or check a classroom psychrometrics problem against a known reference value.

  • Greenhouse setpoint planning: Set a target VPD band for seedling, vegetative, or flowering rooms and read the matching temperature and humidity pair.
  • Indoor air-quality checks: Translate a temperature and relative humidity reading into a vapor pressure deficit that an HVAC controller can act on.
  • Classroom psychrometrics: Work a saturation, actual, and deficit pressure problem set against the FAO-56 reference values without rebuilding the equation by hand.
  • Mold and condensation risk: Read the VPD of a wall, attic, or supply-air stream to judge whether surfaces are close to the dew point.

Vapor pressure deficit is the difference between how much water vapor the air could hold at its current temperature and how much it actually does hold. That gap drives evaporation from a leaf and the moisture exchange between indoor air and a cold window, which is why FAO-56 is cited.

If the reason you are reading a vapor pressure deficit is human thermal comfort, the Heat Index Calculator shows the same temperature and humidity pair as a perceived temperature.

How the Vapor Pressure Deficit Calculator Works

The calculator takes air temperature in degrees Celsius and relative humidity in percent, runs the FAO-56 Magnus-Tetens equation to find saturation vapor pressure, multiplies that by relative humidity to get actual vapor pressure, and subtracts the two to get the deficit.

SVP = 0.6108 x exp(17.27 x T / (T + 237.3)); AVP = SVP x RH/100; VPD = SVP - AVP
  • T (air temperature): Air temperature in degrees Celsius, driving the saturation side through the Magnus-Tetens exponent.
  • RH (relative humidity): Relative humidity as a percent, between 0 and 100. The ratio RH/100 scales the saturation value to the actual vapor pressure.
  • SVP (saturation vapor pressure): Maximum water vapor pressure the air can hold at temperature T, in kPa, from the FAO-56 Annex 2 equation.
  • AVP (actual vapor pressure): Water vapor pressure actually present, equal to SVP times RH/100.
  • VPD (vapor pressure deficit): Difference between SVP and AVP in kPa, with a secondary mbar readout. The driving force for transpiration and evaporation.

Splitting the result into SVP, AVP, and the deficit makes it clear whether the SVP is moving because the temperature changed, or whether the deficit is moving because the humidity shifted, which is the difference between a heating and a humidification problem.

For a greenhouse at 25 degrees C and 60 percent RH: SVP = 3.17 kPa, AVP = 1.90 kPa, VPD = 1.27 kPa = 12.7 mbar, plant-stage band = Flowering. The 1.27 kPa deficit sits inside the 1.0 to 1.6 kPa flowering band, matching the late-vegetative to early-flowering range.

For a cold-storage room at 10 degrees C and 50 percent RH: SVP = 1.23 kPa, AVP = 0.61 kPa, VPD = 0.61 kPa = 6.1 mbar, plant-stage band = Seedling. Cold air holds far less water vapor than warm air, so the same 50 percent humidity produces a much smaller deficit at 10 degrees C, which is why cold frames and propagation rooms read the same numbers on a different temperature scale.

Cold-storage room at 10 degrees C and 50 percent RH

Air temperature: 10 degrees C. Relative humidity: 50 percent.

SVP = 0.6108 x exp(17.27 x 10 / (10 + 237.3)) = 1.23 kPa. AVP = 1.23 x 0.50 = 0.61 kPa. VPD = 1.23 - 0.61 = 0.61 kPa = 6.1 mbar.

VPD = 0.61 kPa, plant-stage band = Seedling.

Cold air holds far less water vapor than warm air, so the same 50 percent humidity produces a much smaller deficit at 10 degrees C, which is why cold frames and propagation rooms read the same numbers on a different temperature scale.

According to FAO Irrigation and Drainage Paper 56, the saturation vapor pressure of air is given by SVP = 0.6108 x exp(17.27 x T / (T + 237.3)) for T in degrees Celsius, with reference values 0.61, 1.23, 2.34, 3.17, and 4.24 kPa at 0, 10, 20, 25, and 30 degrees C.

Once you have the saturation vapor pressure in kPa, the Ideal Gas Calculator handles the related textbook problem of converting between partial pressure, moles, and volume.

Key Concepts Explained

Four ideas sit behind the formula: a temperature-only saturation pressure, a humidity-scaled actual pressure, a deficit that drives evaporation, and a plant-stage band.

Saturation vapor pressure (SVP)

The maximum water vapor pressure the air can hold at its current temperature. SVP rises fast with temperature because warm air holds more moisture, so the FAO-56 reference table lists 1.23 kPa at 10 degrees C and 4.24 kPa at 30 degrees C.

Actual vapor pressure (AVP)

The water vapor pressure actually present in the air, equal to SVP times relative humidity as a fraction. At 25 degrees C and 60 percent RH, AVP is 1.90 kPa, which is 60 percent of the 3.17 kPa SVP at the same temperature.

Vapor pressure deficit (VPD)

The difference between SVP and AVP. VPD is the driving force for evaporation from a wet surface and for transpiration through a leaf stomate, so it is the variable greenhouse controllers and HVAC loops actually target.

Plant-stage band

A plain-text label that maps the VPD number to a horticultural use: seedling (0.4 to 0.8 kPa), vegetative (0.8 to 1.2 kPa), flowering (1.0 to 1.6 kPa), or out of range. The bands are context only, not part of the FAO-56 formula itself.

A 25 degrees C room at 60 percent RH has a 1.27 kPa deficit, while a 30 degrees C room at the same humidity has a 1.70 kPa deficit because the saturation pressure is higher. The vapor pressure deficit calculator makes the same pattern visible at a glance.

For a closer look at the partial-pressure picture behind SVP, the Gas Laws Calculator covers the ideal gas law and Dalton's law.

How to Use This Calculator

Two numbers go in, three pressures and a plant-stage band come out. The default values reproduce the FAO-56 reference condition.

  1. 1 Enter the air temperature: Type the dry-bulb air temperature in degrees Celsius. Use 0.1 degree precision if the sensor is calibrated that fine.
  2. 2 Enter the relative humidity: Type the relative humidity as a percent. Values above 100 are clamped to 100, reproducing a fully saturated air sample.
  3. 3 Read the saturation vapor pressure: The SVP row reports the maximum water vapor the air could hold at the chosen temperature, in kPa.
  4. 4 Read the actual vapor pressure: The AVP row reports the water vapor actually present, equal to SVP times relative humidity as a fraction.
  5. 5 Read the vapor pressure deficit: The VPD row reports SVP minus AVP in kPa, with the same value in mbar underneath.
  6. 6 Check the plant-stage band: The label turns the VPD into a decision: seedling, vegetative, flowering, saturated, or above range.

For a propagation room, set 22 degrees C and 75 percent RH. SVP comes out at 2.64 kPa, AVP at 1.98 kPa, VPD at 0.66 kPa, and the band reads Seedling.

Once you have a target VPD band, the CO2 Grow Room Calculator covers the carbon dioxide side.

Benefits of Using This Calculator

The calculator is most useful when you want the FAO-56 reference answer in seconds and a plain-language band that tells you what to do with it.

  • FAO-56 anchored: Uses the SVP = 0.6108 x exp(17.27 x T / (T + 237.3)) form from FAO-56 Annex 2.
  • Three pressures in one place: Reports saturation, actual, and deficit side by side.
  • kPa and mbar output: Matches the unit most greenhouse and HVAC references use in print.
  • Plant-stage band included: Labels the VPD so the number becomes a decision.
  • Input clamping: Clamps out-of-range humidity entries to 0 or 100 with a small validation message.

These benefits matter most when the calculation is repeated many times a day, as in a propagation room where the operator checks the sensor every hour. The calculator returns the same answer as a printed formula in a fraction of a second.

VPD is one of three indoor-cultivation knobs, and the Daily Light Integral (DLI) Calculator covers the light side.

Factors That Affect Your Results

Two numbers drive the result, and three contextual factors decide whether the resulting VPD is comfortable, productive, or out of range.

Air temperature

SVP grows roughly 7 percent per degree C near room temperature, so a 2 degree C change moves the saturation side by 0.4 to 0.5 kPa and shifts the VPD by almost as much at fixed humidity.

Relative humidity

AVP scales linearly with relative humidity, so halving humidity at the same temperature roughly doubles the VPD. A 60 percent to 30 percent RH step at 25 degrees C raises VPD from 1.27 to 2.12 kPa.

Plant stage

Seedlings, vegetative plants, and flowering plants want different VPD ranges. A 0.5 kPa reading is right for a propagation tray and too low for a flowering room, so the same number reads as comfortable in one context and stressed in another.

Sensor placement

A humidity sensor in direct sunlight, against a cold wall, or near a supply-air vent will read a different microclimate than the room average, so the VPD is only as good as the sensor behind it.

Sub-zero air

Below 0 degrees C the Magnus-Tetens equation still gives a positive SVP, but ice sublimation alters the real behavior, so the low-temperature result is a low-bound approximation rather than a measured value.

  • The Magnus-Tetens equation is accurate within about 0.4 percent for 0 to 50 degrees C. Outside that range the error grows.
  • The plant-stage bands are a teaching aid, not a horticultural prescription. A high-value crop should be tuned against a propagation chart.
  • The calculator does not pull live sensor data. A workflow that needs logging or alerting should pair the calculation with a data acquisition layer.

These caveats matter because the FAO-56 equation is a textbook fit, not a real-world measurement. A propagation tray on a cold concrete bench reads a higher local VPD than the room average, and a leaf transpiring in still air reads a lower local VPD than the same room.

According to Wikipedia: Vapour-pressure deficit, VPD drives transpiration in plants and evaporation in HVAC systems and is the difference between the moisture in the air and the maximum the air could hold at the same temperature.

For a closer look at the heat side of the same indoor air problem, the Heat Transfer Conduction Calculator covers the conductive heat flux through a wall or glazing, the other half of an indoor climate calculation.

Vapor pressure deficit calculator interface showing air temperature, relative humidity, saturation vapor pressure, actual vapor pressure, and vapor pressure deficit outputs
Vapor pressure deficit calculator interface showing air temperature, relative humidity, saturation vapor pressure, actual vapor pressure, and vapor pressure deficit outputs

Frequently Asked Questions

Q: What is a vapor pressure deficit calculator?

A: A vapor pressure deficit calculator is a worksheet that takes air temperature in degrees Celsius and relative humidity in percent and returns three pressures: the saturation vapor pressure the air could hold, the actual vapor pressure it does hold, and the deficit between them, using the FAO-56 Magnus-Tetens equation as the source of truth.

Q: How do you calculate vapor pressure deficit from temperature and relative humidity?

A: Start with SVP = 0.6108 x exp(17.27 x T / (T + 237.3)) for T in degrees Celsius, then compute AVP = SVP x RH / 100, and finally VPD = SVP - AVP. For 25 degrees C and 60 percent RH the result is 1.27 kPa, which is the FAO-56 reference condition.

Q: What is the ideal VPD range for plants?

A: Most greenhouse references place seedlings in the 0.4 to 0.8 kPa range, vegetative plants in 0.8 to 1.2 kPa, and flowering plants in 1.0 to 1.6 kPa. The bands are a teaching aid and should be tuned to the cultivar and the propagation chart on a real grow site.

Q: What is the difference between VPD and relative humidity?

A: Relative humidity is the percent of the saturation pressure that the air currently holds, while VPD is the absolute difference between the saturation pressure and the actual pressure. Two rooms with the same 60 percent RH can have very different VPDs because the saturation pressure itself changes with temperature.

Q: Does VPD change with temperature if humidity stays the same?

A: Yes. SVP grows roughly 7 percent per degree C near room temperature, so raising the temperature at fixed humidity raises VPD by almost the same amount. That is why a 25 degrees C room at 60 percent RH has a 1.27 kPa deficit while a 30 degrees C room at the same humidity has a 1.70 kPa deficit.

Q: Why does VPD matter for greenhouses and indoor grows?

A: VPD is the driving force for transpiration through a leaf stomate, and a transpiration rate that is too low starves the plant of nutrient flow while a rate that is too high causes stomates to close and growth to stall. A controlled VPD keeps the plant in the band where nutrient uptake, CO2 uptake, and temperature regulation all stay in balance.