Mixed Air Calculator - Mixed Air Temperature, Humidity & Enthalpy
Use this mixed air calculator to blend outdoor and return airstreams using ASHRAE psychrometric equations for temperature, humidity ratio, and enthalpy.
Mixed Air Calculator
Results
What Is Mixed Air Calculator?
A mixed air calculator blends outdoor and return airstreams at different temperatures and humidities into a single mixed air state. It applies mass and energy conservation to deliver the mixed dry-bulb temperature, humidity ratio, specific enthalpy, and the back-calculated relative humidity of the supply air. Engineers use it for cooling coil sizing, economiser setup, indoor air-quality audits, and energy modeling.
- • Cooling coil selection: Confirm the mixed air temperature and humidity ratio entering a chilled-water or DX coil before consulting manufacturer selection software.
- • Economiser control setup: Estimate how much outdoor air to admit at each outdoor temperature while keeping the mixed temperature above the cooling-coil dew point.
- • Indoor air-quality audits: Track outdoor air fraction during minimum outside air measurements and verify compliance with ASHRAE 62.1.
- • Energy modeling: Generate the mixed-air state used by hourly simulation tools as the boundary condition for downstream plant equipment.
The calculation follows the two-stream psychrometric mixing equations in the ASHRAE Handbook (Fundamentals), Chapter 1. Both airstreams mix adiabatically at constant atmospheric pressure, so energy and water mass are conserved.
When the inlet temperatures differ by more than about twenty degrees Celsius, converting volumetric flow to mass flow using the air density calculator gives a noticeably different mixed temperature.
When the inlet temperatures differ by more than about twenty degrees Celsius, converting volumetric flow to mass flow using the Air Density Calculator gives a noticeably different mixed temperature.
How Mixed Air Calculator Works
The calculator applies mass and energy conservation to two adiabatic airstreams. Each inlet state is converted into a humidity ratio using the Magnus-Tetens saturation pressure, then the two states are averaged using their flow rates.
- m_oa, m_ra: Outdoor-air and return-air flow rates in cubic feet per minute or kilograms per second.
- T_oa, T_ra: Dry-bulb temperature of each airstream in degrees Celsius.
- w_oa, w_ra: Humidity ratio of each airstream in kg water per kg dry air.
- h_mix: Moist-air specific enthalpy of the mixed stream in kJ/kg dry air.
The Magnus-Tetens equation P_sat = 0.61078 exp(17.27 T / (T + 237.3)) returns the saturation vapour pressure in kilopascals for a Celsius dry-bulb temperature. The humidity ratio w = 0.622 P_v / (P - P_v) then converts vapour pressure P_v into kilograms of water per kilogram of dry air at atmospheric pressure P.
Specific enthalpy h = 1.005 T + w (2501 + 1.88 T) is the standard ASHRAE moist-air form using 1.005 kJ/(kg K) and 1.88 kJ/(kg K) for the specific heats of dry air and water vapour, and 2501 kJ/kg for the latent heat of vaporisation of water at zero degrees Celsius. Because the equation is linear in w and nearly linear in T over the HVAC range, the mixed enthalpy is also a flow-weighted average of the two inlet enthalpies to within about one percent.
Equal flows of 32 C outdoor air and 24 C, 50 percent RH return air
Outdoor: 1000 CFM at 32 C and 0 percent RH. Return: 1000 CFM at 24 C and 50 percent RH.
T_mix = (1000 x 32 + 1000 x 24) / 2000 = 28 C. The return humidity ratio at 24 C and 50 percent is 0.00943 kg/kg, so w_mix = 0.00472 kg/kg.
Mixed air: 28 C, 19.9 percent relative humidity, humidity ratio 0.0046 kg/kg, enthalpy 40.0 kJ/kg, 50 percent outdoor air.
Mixing dry hot outdoor air with cooler, partly humid return air raises the temperature but drops the relative humidity because warm air at 28 C can hold roughly three times as much moisture as air at 24 C.
According to ASHRAE Handbook (Fundamentals), mixed-air temperature and humidity ratio follow from flow-weighted averaging of the inlet states
The humidity ratio calculation here uses the same Magnus-Tetens saturation pressure and ideal-gas conversion that the Absolute Humidity Calculator uses to report absolute humidity in grams per cubic metre.
Key Concepts Explained
Four psychrometric ideas drive the mixed air calculator: saturation pressure, humidity ratio, specific enthalpy, and conservation of mass and energy across the mixing box.
Saturation Vapour Pressure
The maximum partial pressure of water vapour the air can hold at a given temperature. It rises sharply with temperature, which is why the same moisture gives a low relative humidity at 30 C and a high one at 5 C.
Humidity Ratio
Mass of water vapour divided by mass of dry air, in kg/kg. The calculator averages this property directly.
Specific Enthalpy
Total energy content of moist air per kilogram of dry air, combining sensible heat from temperature and latent heat from water content. Downstream coils and wheels exchange this property.
Adiabatic Mixing
An adiabatic mixing box adds no heat or moisture from outside surfaces, so total energy and total water mass in equals total energy and water mass out.
Each concept feeds the formula chain. Saturation pressure determines the inlet humidity ratios, humidity ratio determines the back-calculated mixed relative humidity, and specific enthalpy is the result that downstream cooling coils remove.
The adiabatic-mixing assumption is strong enough for nearly every commercial air-handling unit but breaks down when condensate forms inside the mixing section.
The Vapor Pressure Deficit Calculator uses the same saturation pressure to express the drying power of the air, which helps explain why mixing two streams does not always produce a simple humidity average.
How to Use This Calculator
Use the mixed air calculator by entering the volumetric flow, dry-bulb temperature, and relative humidity of each airstream. Results update as you type.
- 1 Enter the outdoor-air flow rate: Type the design or measured outdoor-air volumetric flow in cubic feet per minute.
- 2 Set the outdoor dry-bulb temperature and relative humidity: Use the local weather data, design day values, or measured sensor readings.
- 3 Enter the return-air flow rate: Enter the return-air volumetric flow in cubic feet per minute. For a constant-volume system, return flow equals supply flow minus any exhaust.
- 4 Set the return dry-bulb temperature and relative humidity: Use the room or return-air plenum conditions.
- 5 Read the mixed state and outdoor air fraction: The result panel lists mixed temperature, humidity ratio, enthalpy, and the back-calculated mixed relative humidity. The outdoor air fraction equals 100 x m_oa / (m_oa + m_ra).
- 6 Adjust the flows to meet ventilation or coil targets: Increase outdoor CFM to lift the outdoor air fraction, or shift temperatures to estimate mixed states at different operating modes.
A classroom unit handling 5,000 CFM total with 1,000 CFM of outdoor air at 35 C and 30 percent RH and 4,000 CFM of return air at 24 C and 50 percent RH produces 26.2 C mixed air at 45 percent RH and 20 percent outdoor air, which is the boundary condition a downstream chilled-water coil would see at part-load.
Once the mixed air state is known, the Heat Transfer Conduction Calculator can size the downstream heating or cooling coil that brings the supply air to room conditions.
Benefits of Using This Calculator
Using this calculator before coil selection, economiser setup, or energy modeling removes several manual steps and surfaces the property engineers actually need.
- • Single mixed state from two inlet states: Returns dry-bulb temperature, humidity ratio, enthalpy, relative humidity, and the outdoor air fraction at once.
- • ASHRAE-aligned equations: Uses the same Magnus-Tetens saturation pressure and ASHRAE moist-air enthalpy constants.
- • Real-time recompute: Results update on every keystroke so designers can compare design days and damper positions quickly.
- • Outdoor air fraction built in: Reports the percentage of the mixed stream from outside, which feeds ASHRAE 62.1 ventilation compliance.
- • Catches supersaturated mixes early: Caps the mixed relative humidity at 100 percent when warm saturated air meets cool saturated air.
- • Inputs that match field instrumentation: Accepts CFM, degrees Celsius, and percent, the same units carried by most building automation trend logs.
The calculator is most useful at the boundary between the airside and the plant side of an HVAC system. A mixed air temperature that is two degrees Celsius warmer than expected can push a chilled-water coil into dehumidification mode and force the chiller to run longer.
When the barometric pressure is well below 101.325 kilopascals, the gas laws calculator helps justify the pressure correction that the mixed air calculator assumes by default.
When the supply or return fan sits at altitude and the barometric pressure is well below 101.325 kilopascals, the Gas Laws Calculator helps justify the pressure correction that the mixed air calculator assumes by default.
Factors That Affect Your Results
Four factors dominate the accuracy of any such calculator: the inlet temperatures, the inlet relative humidities, the flow split, and the atmospheric pressure used to convert relative humidity to humidity ratio.
Outdoor air temperature
Sets the warm-side anchor of the mix. A 5 C swing in the outdoor temperature typically shifts the mixed temperature by about one degree C.
Return air relative humidity
Drives most of the moisture in the mixed stream. A return-air RH drop from 50 to 40 percent often lowers the mixed humidity ratio more than the outdoor RH change.
Outdoor air fraction
Multiplies the contribution of every outdoor-air property. Doubling the minimum outdoor air setting doubles the outdoor effect on temperature, humidity, and enthalpy.
Atmospheric pressure
Enters the humidity-ratio conversion. Above about 1500 metres elevation the pressure correction shifts the mixed humidity ratio by several percent.
- • The model assumes adiabatic, constant-pressure mixing. If condensate forms inside the mixing section or a heat-recovery wheel leaks, the actual mixed state will differ and should be measured.
- • Volumetric flow is used as a proxy for mass flow. When the inlet temperatures differ by more than about twenty degrees Celsius, convert both flows to kilograms per second using the air-density calculator before averaging.
- • Atmospheric pressure defaults to 101.325 kilopascals. For sites above 1500 metres, set the local barometric pressure explicitly.
- • The Magnus-Tetens saturation pressure approximation is accurate to within about one percent for the 0 to 60 C range used here.
Two practical cautions are worth highlighting. First, mixing two saturated airstreams at very different temperatures can imply a humidity ratio that exceeds saturation at the mixed temperature, so the actual mixed stream sits at 100 percent RH with the excess moisture condensing out. The calculator caps the result at 100 percent to flag this case.
Second, the result panel reports mixed relative humidity back-calculated from the mixed humidity ratio. That value matches the formula chain, but a real mixed-air sensor will only agree closely when the mixing box truly behaves as an adiabatic, well-mixed plenum.
According to Wikipedia: Psychrometrics, psychrometric mixing conserves both energy and water mass when the process is adiabatic
Third, projects sitting above about 1500 metres of elevation should enter the local barometric pressure explicitly; the Boiling Point Altitude Calculator converts a measured station pressure into the equivalent altitude for that check.
Frequently Asked Questions
Q: What is the mixed air calculator formula?
A: The mixed dry-bulb temperature is the flow-weighted average T_mix = (m_oa T_oa + m_ra T_ra) / (m_oa + m_ra), and the mixed humidity ratio is the same flow-weighted average w_mix = (m_oa w_oa + m_ra w_ra) / (m_oa + m_ra). Mixed enthalpy then follows from h = 1.005 T_mix + w_mix (2501 + 1.88 T_mix) per the ASHRAE Handbook (Fundamentals).
Q: How do you calculate mixed air temperature from outdoor and return air?
A: Convert both flow rates to the same unit, multiply each flow by its dry-bulb temperature, sum the two products, and divide by the total flow. The result is the mixed dry-bulb temperature; the same procedure with humidity ratios in place of temperatures gives the mixed humidity ratio.
Q: Does the mixed air humidity depend on temperature or flow rate?
A: Both. The mixed humidity ratio depends on the two inlet humidity ratios and their flow rates; the back-calculated mixed relative humidity then also depends on the mixed dry-bulb temperature through the saturation pressure curve.
Q: What is the outdoor air fraction in HVAC mixed air?
A: Outdoor air fraction equals 100 times the outdoor-air flow divided by the sum of outdoor and return flows. ASHRAE 62.1 calls this the percentage of outside air and uses it to verify that minimum ventilation rates are being delivered to the occupied space.
Q: Can mixed air relative humidity exceed 100 percent?
A: The arithmetic can produce a value above 100 percent when two saturated airstreams at very different temperatures are mixed, but physically the excess moisture condenses and the actual stream sits at 100 percent RH. The calculator caps the result at 100 percent and flags the case as supersaturated.
Q: Why does mixing air at two temperatures not give the simple average?
A: The flow-weighted average of the temperatures does give the dry-bulb temperature, but the same simple average applied to relative humidity is wrong because relative humidity depends nonlinearly on temperature. The calculator converts each RH to a humidity ratio first, averages the ratios, and back-calculates the RH at the mixed temperature.